Kyoritsu, 6010A
Le foto sono di repertorio e potrebbero non corrispondere all'oggetto realmente venduto, come pure le opzioni installate. Su richiesta verranno fornite foto in alta risoluzione e opzioni reali dell'oggetto in vendita.
Descrizione del prodotto
Tester digitale multifunzioneTest di Continuità e d'isolamento:
- Live circuit warning LED:
- Immediate illumination of a warning lamp if the circuit under test is live
- Auto Discharge:Allows fast and safe discharge of electrical energy stored in capacitive circuits following testing
- Integral overload protection on internal continuity and insulation test circuitry
- Autoranging
- 500V DC test voltage for insulation tests
- 200mA short circuit current on continuity ranges
LOOP e RCD test:
- Wiring connection check LED’s: Immediate indication if wiring of circuit under test is correct
- Overheat Protection: Rapid detection of overheating of internal circuitry,display of warning signal to user and automatic halting of measurement
- Supply Voltage Indication: Can display supply voltage value in loop impedance mode
- Low Current Loop Impedance Test: Short duration low test current will prevent tripping of many passive RCDs
- Auto Data Hold: Retains displayed reading for set period following test
- Phase Angle Selection: Selection of test current from +ve or -ve half cycle of waveform can prevent tripping of polarized type RCDs
Caratteristiche
Continuity Testing:
- Measuring Ranges 0~19.99 and 10.0~199.9Ω (2 auto ranges)
- Open Circuit Voltage > 4V (as per IEC 364)
- Short Circuit Current > 200mA DC (as per IEC 364)
- Accuracy |±(3% + 3dgt)
Loop Impedance Testing:
- Rated Voltage 230V AC +10%-15% (50Hz)
- Voltage Measuring Range 100-250V AC (50Hz)
- Impedance Range 20/2000Ω
- Nominal Test Current 25A (20Ω range) 15mA (2000Ω range)
- Test Period 1/2 cycle (10ms)
- Accuracy 20Ω range : ±(3% + 8dgt) 2000Ω range : ±(3% + 8dgt)
Insulation Testing:
- Measuring Ranges 0~19.99 and 10.0~199.9MΩ (2 auto ranges)
- Test Voltage 500V DC
- Output Voltage on Open Circuit 570V DC±6%
- Rated Current > 1mA (as per IEC 364)
- Accuracy |± (3% + 3dgt)
RCD Testing
- Rated Voltage 230V AC +10%-15% (50Hz)
- Trip Current Settings RCD × 1/2: 5, 15, 50, 150, 250mA RCD × 1: 10, 30, 100, 300, 500mA
- Trip Current Duration RCD × 1/2 × 1: 2000ms
- Fast Trip 150mA
- Accuracy Trip current ±3% of test current at 230V.
- Trip time ±(3% + 3dgt)