Tester digitale multifunzione

Test di Continuità e d'isolamento:
  • Live circuit warning LED:
  • Immediate illumination of a warning lamp if the circuit under test is live
  • Auto Discharge:Allows fast and safe discharge of electrical energy stored in capacitive circuits following testing
  • Integral overload protection on internal continuity and insulation test circuitry
  • Autoranging
  • 500V DC test voltage for insulation tests
  • 200mA short circuit current on continuity ranges

 LOOP e RCD test:
  • Wiring connection check LED’s: Immediate indication if wiring of circuit under test is correct
  • Overheat Protection: Rapid detection of overheating of internal circuitry,display of warning signal to user and automatic halting of measurement
  • Supply Voltage Indication: Can display supply voltage value in loop impedance mode
  • Low Current Loop Impedance Test: Short duration low test current will prevent tripping of many passive RCDs
  • Auto Data Hold: Retains displayed reading for set period following test
  • Phase Angle Selection: Selection of test current from +ve or -ve half cycle of waveform can prevent tripping of polarized type RCDs

Caratteristiche
Continuity Testing:
  • Measuring Ranges 0~19.99 and 10.0~199.9Ω (2 auto ranges)
  • Open Circuit Voltage > 4V (as per IEC 364)
  • Short Circuit Current > 200mA DC (as per IEC 364)
  • Accuracy |±(3% + 3dgt)
Loop Impedance Testing:
  • Rated Voltage 230V AC +10%-15% (50Hz)
  • Voltage Measuring Range 100-250V AC (50Hz)
  • Impedance Range 20/2000Ω
  • Nominal Test Current 25A (20Ω range) 15mA (2000Ω range)
  • Test Period 1/2 cycle (10ms)
  • Accuracy 20Ω range : ±(3% + 8dgt)   2000Ω range : ±(3% + 8dgt)
Insulation Testing:
  • Measuring Ranges 0~19.99 and 10.0~199.9MΩ (2 auto ranges)
  • Test Voltage 500V DC
  • Output Voltage on Open Circuit 570V DC±6%
  • Rated Current > 1mA (as per IEC 364)
  • Accuracy |± (3% + 3dgt)
RCD Testing
  • Rated Voltage 230V AC +10%-15% (50Hz)
  • Trip Current Settings RCD × 1/2: 5, 15, 50, 150, 250mA RCD × 1: 10, 30, 100, 300, 500mA
  • Trip Current Duration RCD × 1/2 × 1: 2000ms
  • Fast Trip 150mA
  • Accuracy Trip current ±3% of test current at 230V.
  • Trip time ±(3% + 3dgt)